What size garage heater do I need? 18 heaters from 5 makers

Garage heater size in BTU and watts from your garage's size and winter low, with 18 current electric and gas garage heaters from Dr. Heater, Fahrenheat, King Electric, Modine, Mr. Heater, each maker's rating, wiring and coverage claim.

Ratings, wiring and coverage claims read by hand on each maker's product page or manual on 21 October 2026. We have not installed or measured any of these heaters. How we research | How links work

The short answer

A typical two-car garage, 24 x 24 ft with an 8 ft ceiling, needs about 24,500 BTU/hr of heat output to stay 40°F warmer than outside, by the common rule of cubic feet x 0.133 x temperature rise. That is a 7,500 W electric heater on a 240 V circuit or a gas unit heater with about 25,000 BTU/hr of output, which is 30,000 BTU/hr of input on Modine's Hot Dawg. Makers disagree: King Electric's own chart asks for about half that wattage in a well insulated garage, so match the rule to your walls and door.

Title card: what size garage heater, with rising bars
Illustration, not a photograph of a specific product.

Size a heater for your garage

Enter the inside size of your garage, how cold it gets outside, and how warm you want it. The rise is the difference between the two.

About 24,515 BTU/hr

24 x 24 x 8 ft at a 40°F rise: 4,608 cubic feet x 0.133 x 40.

Every heater: electric by watts, then gas by input

Electric output is watts x 3.413, since all of an electric heater's power becomes heat. Gas output is the maker's own figure where it gives one. "Covers by the rule" is the floor area each heater holds at a 40°F rise with an 8 ft ceiling, by the 0.133 rule. Amps marked "ours" are watts / 240. Empty cells mean the maker does not give the figure on the page we read.

HeaterFuelWattsGas input (BTU/hr)Output (BTU/hr)Amps at 240 VWiring or circuit as statedMaker's coverage claimCovers by the rule (sq ft)NoteSource
Fahrenheat FUH54CElectric, 240 V5,00017,06520.930 A fuse (maker table); 208 V gives 3,750 W401Maker states 17,065 BTU/hr at 240 VFahrenheat
King Electric GH2405TBElectric, 240 V5,00017,06520.8240/208 V; 13% fewer amps at 208 V401Maker states 17 kBTUHKing Electric
Dr. Heater DR-988Electric, 240 V5,60019,11323.3 (ours)Plug-in: NEMA 6-30P on a dedicated 30 A 250 V outlet449The only plug-in model here; the rest are hardwiredDr. Heater
Dr. Heater DR-966Electric, 240 V6,000 (3,000 W low setting)20,47825.0 (ours)Hardwired; 8 AWG copperHeating coverage: 600 sq ft481Dr. Heater
Dr. Heater DR-975Electric, 240 V7,500 (4,700 W low setting)25,59831.3 (ours)Hardwired; 8 AWG copper601Dr. Heater
Fahrenheat FUH724AElectric, 240 V7,50025,59831.345 A fuse (maker table); 208 V gives 5,625 W601Maker states 25,598 BTU/hr at 240 VFahrenheat
King Electric GH2407TBElectric, 240 V7,50025,59831.2240/208 V601Maker states 25.6 kBTUHKing Electric
Dr. Heater DR-910FElectric, 240 V10,00034,13041.7 (ours)Hardwired; 6 AWG copper802Dr. Heater
Dr. Heater DR-910MElectric, 240 V10,00034,13041.7 (ours)Hardwired; 6 AWG copper; on a cart802Dr. Heater
King Electric GH2410TBElectric, 240 V10,00034,13041.6240/208 V802Maker states 34.1 kBTUHKing Electric
Modine Hot Dawg HD30Natural gas or propane, vented30,00024,9001 to 1-1/2 car garage585Modine and FAQ
Modine Hot Dawg HD45Natural gas or propane, vented45,00037,3502 to 2-1/2 car garage878Modine and FAQ
Mr. Heater Big Maxx MHU50Natural gas or propane, vented50,000Heats up to 1,667 sq. ft.under 1,175Output not stated on the product page; natural gas, propane kit includedMr. Heater
Modine Hot Dawg HD60Natural gas or propane, vented60,00049,8003 to 3-1/2 car garage1,170Modine and FAQ
Modine Hot Dawg HD75Natural gas or propane, vented75,00062,250Larger garages and higher altitudes1,463Modine and FAQ
Mr. Heater Big Maxx MHU80Natural gas or propane, vented80,000Heats up to 2,667 sq. ft.under 1,880Output not stated on the product pageMr. Heater
Modine Hot Dawg HD100Natural gas or propane, vented100,00082,000Larger garages, out-buildings and higher altitudes1,927Modine and FAQ
Modine Hot Dawg HD125Natural gas or propane, vented125,000102,500Larger garages, out-buildings and higher altitudes2,408Modine and FAQ

For the example garage, 12 of the 18 heaters have a stated or computed output of at least 24,515 BTU/hr. The smallest electric ones are the 7,500 W models: Dr. Heater DR-975, Fahrenheat FUH724A, King Electric GH2407TB. Mr. Heater gives input but not output on its Big Maxx pages, so its "covers" figure is an upper limit.

Two coverage claims are generous by the rule. Dr. Heater states 600 sq ft for the 6,000 W DR-966; by the rule that holds a rise of about 32°F at an 8 ft ceiling, not 40°F. Mr. Heater states 1,667 sq ft for the 50,000 BTU/hr MHU50; even if every BTU of input reached the garage, the rule gives a rise of about 28°F. Modine's claims are closer: the HD45's 37,350 BTU/hr output holds a 700 sq ft two-car garage at about a 50°F rise.

Makers' sizing rules side by side

King Electric's chart is for a 60°F rise in a garage "adequately insulated for the local climate". The 0.133 rule is the one Ferrellgas publishes and the top sizing calculators use; it makes no insulation allowance. Same garage sizes, both in watts:

Ceiling1-car, 450 sq ft: King chart (W)2-car, 700 sq ft: King chart (W)3-car, 900 sq ft: King chart (W)4-car, 1100 sq ft: King chart (W)1-car: 0.133 rule (W)2-car: 0.133 rule (W)3-car: 0.133 rule (W)4-car: 0.133 rule (W)Source
8 ft4,4006,8509,10011,7508,41713,09316,83420,575King, rule
10 ft4,8507,50010,90012,95010,52216,36721,04325,719King, rule
12 ft5,3008,20012,60014,10012,62619,64025,25230,863King, rule

The rule asks for 1.9 times King's wattage for a two-car garage at an 8 ft ceiling. Neither is wrong for its own assumption. If your garage door is bare steel and the walls are open studs, the rule is the safer number. If the walls, ceiling and door are insulated, King's chart is closer. Modine and Mr. Heater state coverage by car count or floor area without a rise or insulation level, so they cannot be checked the same way.

Next step

Measure your garage inside the walls, decide how warm you need it, and check your panel has room for a 240 V breaker of the size on the heater's label. For gas, confirm the venting and gas line with the maker's installation manual before you buy.

Common questions

What size heater do I need for a 2-car garage?

About 24,500 BTU/hr of heat output for a 24 x 24 ft garage with an 8 ft ceiling and a 40°F rise, by the common rule of cubic feet x 0.133 x temperature rise. That is about a 7,200 W load, so a 7,500 W electric heater such as the Fahrenheat FUH724A (25,598 BTU/hr), or a gas unit with at least that output, such as the Modine Hot Dawg HD30 (24,900 BTU/hr output). A colder target or poor insulation needs more.

Why do makers' own sizing charts disagree?

They assume different garages. King Electric's chart gives 6,850 W for a 700 sq ft two-car garage with an 8 ft ceiling at a 60°F rise, for a garage "adequately insulated for the local climate". The 0.133 rule gives 13,093 W for the same garage, about 1.9 times as much. Use the chart that matches your insulation, and size up if your door and walls are bare.

Is a 30,000 BTU gas heater enough for a 2-car garage?

Check the output, not the input. Modine rates its Hot Dawg HD30 at 30,000 BTU/hr input and 24,900 output and lists it for a 1 to 1-1/2 car garage. It lists the HD45 (37,350 output) for 2 to 2-1/2 cars.

What circuit does a 240 V garage heater need?

It depends on the watts. Fahrenheat's manual lists a 30 A fuse for the 5,000 W FUH54C and 45 A for the 7,500 W FUH724A. Dr. Heater specifies 8 AWG copper for its 6,000 and 7,500 W models and 6 AWG for 10,000 W, and its plug-in DR-988 needs a dedicated 30 A NEMA 6-30 outlet. Have an electrician size the circuit to the label and local code.

Method

  1. Models. Garage heaters from Dr. Heater, Fahrenheat, King Electric, Modine, Mr. Heater that sit on a 240 V circuit or a gas line, read one page or manual at a time on 21 October 2026. Plug-in 120 V heaters and portable propane heaters are not included.
  2. Load. Cubic feet x 0.133 x temperature rise, in BTU/hr. Example: 24 x 24 x 8 = 4,608 cubic feet; x 0.133 x 40 = 24,515 BTU/hr. Divide by 3.413 for watts.
  3. Output. Electric: watts x 3.413. Gas: the maker's stated output (Modine). Where a gas maker gives only input (Mr. Heater), we compare the input and say so.
  4. Claims. Each maker's coverage claim is copied as written. The rise each claim implies is the output divided by (floor area x 8 ft x 0.133).
  5. Not covered. Heat loss from your actual walls, door and air leaks, which a heat-loss calculation by an HVAC contractor would measure. Venting, gas line sizing and electrical code. We did not test any heater.

Sources

Changes

  • : Published. 18 garage heaters from Dr. Heater, Fahrenheat, King Electric, Modine, Mr. Heater, each read on the maker's page or manual on 21 October 2026, with King Electric's sizing chart and the 0.133 rule side by side.